Fire detector IP 101 1a a3. Purpose and scope





Description Siberian Arsenal IP-101-1A-A3

Siberian Arsenal IP-101-1A-A3 is a maximum fire thermal detector that is used to detect signs of fire (increased ambient temperature). An alarm is generated when the temperature reaches environment threshold value.

The detectors are designed for round-the-clock operation in closed heated rooms and are designed to work together with control and control devices with direct or alternating current loops.

The detector has a microprocessor analysis of the temperature sensor signal, periodically measures the ambient temperature and, when a threshold temperature value is reached, generates an alarm by increasing the current consumption. For easy control of operation there is a red LED indicator. In standby mode, the indicator gives short flashes at intervals of 6...8 s. In alarm mode, the LED indicator in IP101-1A-A3 detectors gives double and triple flashes, respectively, with a frequency of 1 Hz. This makes it easy to detect a triggered detector. Devices of this type receive power directly through the alarm loop, eliminating the need for additional power line wires. Possibility of connecting detectors to an alarm loop without observing polarity, as well as connecting fire alarm control and control devices “Granit”, “Karat”, “UTS-1-1A”, “Kvarts” to fire loops without using external limiting resistors.

The aesthetic design of the detector housing fits into the interior of any room.

Technical characteristics Siberian Arsenal IP-101-1A-A3

  • Unit: 1 piece
  • Dimensions (mm): 62x62x34
  • Weight (kg): 0.02
  • The polarity of the supply voltage is arbitrary
  • Rated operating temperature +64...+76 °С
  • Response time when temperature rises at a rate of 3 °C/min* 770 ±190 s
  • Interval between temperature measurements 6...8 s
  • Time to return to standby mode after removing the supply voltage, at least 2 s
  • Loop supply voltage 10...25 V
  • Permissible loop closure current in alarm mode, no more than 20 mA
  • Current consumption in standby mode, no more than 85 μA
  • Residual voltage in “Fire” mode (internal), no more than 8.5 V
  • Shell protection degree IP30
  • Operating temperature range -10...+76 °C
  • Mean time between failures 70,000 hours
  • Service life: at least 10 years

The maximum thermal fire detector IP 101-1A-A3 is required for operation in an integrated fire alarm and fire extinguishing system. Its continuous operation ensures high level fire protection. WITH elevated temperature response: +64°C...+76°C

Maximum thermal fire detector IP101-1A-A3:

Additional devices in security and fire alarm system IP series have stable characteristics and belong to the category of “Universal auxiliary devices”.

  • 24/7 operation;
  • Is integral part comprehensive fire protection;
  • Connects to control devices powered by direct or alternating current;
  • Any polarity when connecting;
  • The smoke detector is triggered when a certain ambient temperature is reached

A wide range of devices allows you to choose a model to suit any request and functionality. Big choice will please companies involved in the installation of fire and fire protection systems burglar alarm and their Customers.

Technical characteristics of IP 101-1A-A3

PARAMETER NAME PARAMETER VALUE
Detector type

2 wire

Response temperature +64°C...+76°C
Light indication ″Standby mode″; "Fire"
Supply voltage via alarm loop 10 - 25 V
Current consumption in standby mode 0.06 mA
Dimensions (diameter/height) 62/34 mm
Degree of protection IP30
Operating temperature range -10°C...+76°C
Weight 0.02 kg
Equipment:
  • Detector IP 101-1A-A3 (IP 101-1A-A3)
  • Passport SAPO.425212.004PS
  • Alarm system for office;
  • Fire alarm for cafes and clubs;
  • Alarm in the store;
  • Fire systems for warehouses and office premises;
  • Autonomous fire alarm for an apartment, house or cottage;
  • Fire alarm for covered parking lots, garages and parking lots;
  • Comprehensive fire protection for government institutions (kindergartens, schools, other educational institutions)

When choosing, pay special attention to careful study technical characteristics, selection of suitable security detectors, fire detectors, special cable products. IP line devices are one of the best in terms of price-quality ratio and are recommended for use in wide-spectrum security and fire alarm systems.

Analogues of IP 101-1A-A3 and other devices with similar characteristics:

Buy and order delivery of fire alarm systems in Moscow:

Maximum thermal fire detector IP101-1A-A3, as well as other products (their analogs, detectors, control devices) you can order and buy through the online fire alarm store of our website or order delivery and professional installation services in your premises in Moscow in ABars company. (Attention, delivery is free for orders over 60 thousand rubles).

Thermal detector 54°C, with indicator

Purpose

The fire thermal maximum detector "IP101-1A-A1" is used to detect signs of fire (increased ambient temperature). An alarm is generated when the ambient temperature reaches a threshold value.

The detectors are designed for round-the-clock operation in closed heated rooms and are designed to work together with control and control devices with direct or alternating current loops.

Peculiarities

  • Microprocessor analysis of temperature sensor signal
  • The detector periodically measures the ambient temperature and, when a threshold temperature value is reached, generates an alarm by increasing the current consumption.
  • For easy control of operation there is a red LED indicator. In standby mode, the indicator gives short flashes at intervals of 6...8 s. In alarm mode, the LED indicator in IP101-1A-A1 detectors gives double and triple flashes, respectively, with a frequency of 1 Hz. This makes it easy to detect a tripped detector
  • The detectors receive power directly through the alarm loop, eliminating the need for additional power line wires
  • The design of the detectors ensures their connection to the alarm loop without observing polarity
  • Possibility of connecting “Granit”, “Karat”, “Quartz” alarm and fire alarm control and control devices to fire loops without the use of external limiting resistors
  • The aesthetic design of the detector housing fits into the interior of any room

Specifications

Supply voltage polarityfree
Rated response temperature+54...+65 °С
Response time when the temperature rises at a rate of 3 °C/min*700 ±120 s
Interval between temperature measurements6...8 s
Time to return to standby mode after removing the supply voltage, not less2 s
Supply voltage range from the alarm loop,10...25 V
Current consumption60 µA
Residual voltage in “Fire” mode (internal), no more5.5 V
Shell protection degreeIP30
Operating temperature range-30...+76 °С
Average time between failures of the device in security mode or disarming mode, not less70,000 hours
Service life, not less10 years

PASSPORT

Maximum thermal fire detectors IP 101-1A-A1, IP1 01-1A-A3 (hereinafter referred to as detectors) are designed to operate as part of automatic fire alarm systems.
fire extinguishing and fire alarm systems. In terms of temperature and response time, detectors IP 101-1A-A1 and IP 101-1A-A3 belong to classes A1 and A3 NPB 85-2000, respectively. The detectors are designed for continuous round-the-clock operation in closed heated rooms together with control and control devices that have a fire alarm loop (FAL) of direct or alternating current. The polarity of connecting the detector to the ShPS can be arbitrary. Detectors issue a “Fire” signal to the alarm loop by increasing the current consumption when the ambient temperature is exceeded
air of the set threshold value. The detector has LED indication of the standby mode and the “Fire” mode.
The detector implements a microprocessor analysis of the temperature sensor signal, which makes it possible to achieve high precision and low inertia
triggering over the entire range of temperature rise rates. The detector provides the ability to connect devices to the ShPS
security and fire alarm control panels (PPKOP) “Granit”, “Karat”, UOTS-1-1A, “Kvarts” without the use of external limiting resistors. An external resistor connected to an additional contact of the terminal connector can be used to connect other control panels to the ShPS.
The detector is not intended for use in chemically aggressive environments. The design of the detector is ordinary according to GOST 12997-84 for operation in
temperature range from minus 10 C to + 76 C and relative air humidity up to 93% at a temperature of + 40 C. Degree of protection of the shell detector
which IP30 according to GOST 14254-96.

Design and principle of operation
Structurally, the detectors are made in a plastic case, consisting of a base and a decorative protective cover with a protruding lattice compartment. There are three screw terminals on the base for connecting the detector to the ShPS line and installing, if necessary, additional relay
stora. At the edges of the decorative cover there are two mounting holes for mounting the detector on the protected object.
In standby mode the temperature external environment measured by the detector discretely, during short time intervals, following with a period of 6...8
seconds Each measurement is accompanied by a short flash of the red LED indicator.
When the ambient temperature threshold value is reached, the detector switches to the “Fire” mode. In this mode, the residual voltage (between terminals 1 and 2) at a current of up to 20 mA does not exceed 8.5 V. The LED indicator in the IP 101-1A-A1 and IP 101-1A-A3 detectors gives double and triple flashes, respectively, with a frequency of 1 Hz
Detectors retain the “Fire” state after the end of exposure
elevated temperature. Switching the detector to standby mode

Peculiarities:
Electronic circuit management.
The detector periodically measures the ambient temperature and, when the temperature threshold is reached, generates an alarm by closing the alarm loop.
For easy monitoring of the detector operation, there is a red LED indicator. In standby mode, the indicator gives short flashes at intervals of 8 s. In alarm mode, the indicator lights up constantly, which makes it possible to easily detect a triggered detector.
The detector receives power directly through the alarm loop, eliminating the need for additional power line wires.

Supply voltage polarity

free

Loop supply voltage

10...25 V

Average current consumption in standby mode, no more

0.05 mA

Permissible loop closure current in alarm mode, no more

20 mA

Residual voltage of the closed loop no more

4.5 V

Rated response temperature

70 ± 6 °С

Interval between temperature measurements

8 s

Time to return to standby mode after removing the supply voltage, no more

5 s

Protected surface, not less

25 sq.m

Operating temperature range

0...+55 °С

Weight, no more

100 g

Shell protection degree

IP30

Service life, not less

10 years

The maximum thermal fire detector IP101-1A complies with the requirements of NPB 76-98 and is designed to issue a signal to the fire alarm loop (FAL) by closing the loop when the ambient air temperature reaches a threshold value.

The detector is designed for continuous round-the-clock operation in closed heated rooms.

The detector is designed to work together with control and control devices (PKP) that receive a signal about the closure (SPS) and have a direct or alternating current loop.

The detector is not intended for use in chemically aggressive environments.

The design of the detector is ordinary according to GOST 12997-84.
Type of climatic modification - UHL category 3.1 according to GOST 15150-69 for operation in the temperature range from 0C to + 50C and relative air humidity up to 95% at a temperature of +35C.

The nominal value of the detector response temperature is +70C. The deviation of the detector response temperature from the nominal value is no more than 5%.

The inertia of the detector response (the time of rise of the ambient temperature from +25C until the moment the detector is triggered) at a temperature rise rate of 30C/min is within 39...162 seconds. The response time of the detector at a temperature rise rate of 3C/min is within the range of 433...1120 sec.

The detector is powered via the ShPS directly from the control panel. Supply voltage range from 10 to 25 V.

Current consumption in standby mode is no more than 50 µA.

The protected surface is at least 25 sq.m. Indication of standby and alarm modes.

Electronic control circuit. The detector periodically measures the ambient temperature and generates an alarm when a threshold temperature value is reached.
For easy monitoring of the detector operation, there is a red LED indicator.
In standby mode, the indicator gives short flashes at intervals of 8 s. In alarm mode, the indicator lights up constantly, which makes it possible to easily detect a triggered detector. The detector receives power directly through the alarm loop, eliminating the need for additional power line wires.
The design of the detector ensures its connection to the alarm loop without observing polarity.
The aesthetic design of the detector housing fits into the interior of any room.