Water heating boilers BOSCH UNIMAT UT-L. Industrial boilers Simple and convenient control

The power range of UNIMAT UT-L three-pass fire-tube boilers is from 750 to 19,200 kW. Designed to work with gas, diesel and combined burners.
UT-L boilers are available in modifications for 2500, 3050, 3700, 4200, 5200, 6500, 7700, 9300, 11200, 12600, 14700, 16400, 19200 kW.

Application area

Boilers type UT-L are perfect solution for heat supply systems, including city main networks. The UT-L model is particularly used in hospitals, multi-apartment residential buildings, office buildings, as well as at various industrial enterprises. In addition, the UT-L boiler is ideal for use as a reserve or peak boiler in thermal power plants.

Reliable technology

The reliability of the three-pass design of Unimat UT-L boilers has been repeatedly proven by examples of their long-term use in 140 countries around the world. The hot water boiler is CE marked and its design and equipment complies with the European Pressure Vessel Directive. The boiler is certified in accordance with the requirements Technical regulations Customs Union and is intended for use at temperatures up to 110 °C and pressures up to 16 bar.

High level of efficiency

High-quality mineral wool surface insulation minimizes radiation losses. At the customer's request, the boiler can be equipped with a built-in or free-standing economizer, as well as a condensing heat exchanger. Standard calculated efficiency without a flue gas heat exchanger is up to 95% and up to 105% when using a condensing heat exchanger.
Low level of emissions of harmful substances due to the use modern systems combustion and the optimal combination of boiler and burner. Compatible with burner devices from many manufacturers.

Installation and Maintenance

Compact design to facilitate delivery of the boiler to the site in case of limited space. Easy commissioning thanks to pre-parameterized boiler control. Simplified installation of wiring at the boiler installation site thanks to plug-in connections. Easy maintenance, cleaning and inspection thanks to the fully openable front door of the boiler. Depending on customer preferences, hinges can be located on the left or right. Smoke pipes without turbulators.

Simple and convenient control

Intelligent control and regulation systems provide additional features to save energy. Compact and accessible system Control 8000 with intuitive touch screen. Alternatively, for complex boiler systems, a BCO boiler control system can be selected.

File name Valid until Download
Certificate of Conformity RU_С-RU.МО09.B.00107_RU until June 25, 2022 Download (JPG 0.6 MB)
Certificate of conformity RU_С-RU.МО09.B.00089_RU until 04/03/2022 Download (PDF 0.4 MB)
Certificate of Conformity RU_С-RU.МО09.B.00026_RU until March 28, 2021 Download (PDF 1.4 MB)
Product Brochure Download (PDF 3.3 MB)
Declaration of Conformity until June 25, 2022 Download (PDF 0.4 MB)
Certificate of conformity TS010 until 10/14/2023 Download (PDF 0.9 MB)
Certificate of conformity TS016 until 10/14/2023 Download (PDF 0.9 MB)
Questionnaire template Download (PDF 0.2 MB)
User manual Download (PDF 9.0 MB)
Specifications Download (PDF 0.2 MB)
Main dimensions Download (PDF 0.6 MB)

Equipment level

The UNIMAT UT-L water heating boiler is offered as a fully functional unit complete with associated components. The equipment configuration can be freely varied and configured in accordance with customer requirements. The basic set of high-quality equipment includes the boiler body, burner unit, flue gas heat exchanger or condensing heat exchanger, as well as the control system and connected safety devices and the compact Control 8000 system.
As an alternative, it is also possible to select a BCO boiler control system together with a control cabinet. All wire connections are already made in the built-in terminal block. Pre-installed, marked cable harnesses simplify the electrical installation of the boiler control cabinet with terminal box.

Equipment

  • Control 8000 control system (alternatively: BCO boiler control system inside the control cabinet)
  • Direct flow pipe complete with necessary equipment
  • Safety valves
  • Return flow pipe complete with necessary equipment
  • Exhaust gas heat exchanger ECO
  • Burner device
  • Gas train
  • Support frame
  • Insulation with sheathing
  • Shut-off drain valve
  • Terminal box
  • Inspection hole
  • Injection device
  • Viewing hole from the side flue gases

Related boiler room components

  • WTM water softening module
  • Exhaust gas heat exchanger ECO 1/7
  • Exhaust gas heat exchanger ECO 6 condensing
  • Intermediate flow/return connection SP/RP
  • Return temperature increase device RTS
  • Module with gas regulator GRM
  • Circulation module liquid fuel OCM
  • Liquid fuel supply module OSM
  • SCO control system
UT-L UT-L UT-L
Boiler size 18 24 28
2500 3050 3700
2734 3350 4020
Transport weight, kg 4460 4880 5940
Boiler length, mm 3675 3725 4075
Boiler width (total), mm 1574 1674 1724
Boiler width, mm - - -
- - -
Overall height, mm 1930 2030 2080

Industrial heating water boilers Unimat UT-L UT-L UT-L UT-L
Boiler size 30 34 40
Nominal heating capacity, kW 4200 5200 6500
4578 5675 7147
Transport weight, kg 7530 8480 10500
Boiler length, mm 4570 4700 5090
Boiler width (total), mm 1824 1924 2124
Boiler width, mm - - -
Burner door opening area, mm - - -
Overall height, mm 2180 2280 2480

Industrial heating water boilers Unimat UT-L UT-L UT-L UT-L
Boiler size 42 46 50
Nominal heating capacity, kW 7700 9300 11200
8403 10118 12190
Transport weight, kg 12830 14630 18770
Boiler length, mm 5320 5520 5980
Boiler width (total), mm 2274 2424 2574
Boiler width, mm - - -
Burner door opening area, mm - - -
Overall height, mm 2630 2790 2940

Industrial heating water boilers Unimat UT-L UT-L UT-L UT-L
Boiler size 54 58 60/64
Nominal heating capacity, kW 12600 14700 16400/19200
13635 16000 17620/20758
Transport weight, kg 21100 25970 33390/38690
Boiler length, mm 6315 7050 7530/7980
Boiler width (total), mm 2724 2924 3224/3424
Boiler width, mm - - -
Burner door opening area, mm - - -
Overall height, mm 3090 3300 3600/3800

The reliability of the three-pass design of Unimat boilers has been repeatedly proven by examples of their practical application in 140 countries of the world. Fire tube hot water boilers of the UNIMAT series are offered in various sizes and can operate in cascade.


Boilers of the UT-L type can be used in hospitals, private and multi-apartment residential buildings, office buildings, as well as industrial enterprises. Thanks to its high degree of versatility, the UT-L can be used as a backup boiler or used to cover peak loads.


Design:

The flame pipe ends with a rotating chamber of flue gases, washed by water, which passes into the second passage of the smoke pipes. In total, the boiler has three heat exchange passes: the first - in the boiler furnace (radiant heat exchange), the second and third - in the smoke tubes of the boiler (convective). The arrangement of smoke pipes in a circle ensures optimal flow of flue gases. Smoke pipes do not have internal turbulators, which create additional resistance to the movement of combustion products. The combustion chamber, water space, radiant and convective heating surfaces are optimized and mutually coordinated.

The front door of the boiler opens completely. Depending on customer preferences, hinges can be located on the left or right. Thanks to the fully openable boiler door, complete maintenance, cleaning and inspection can be carried out. The absence of turbulators in the pipes of the second and third stroke reduces the labor intensity and time costs of carrying out routine maintenance maintenance boiler High-quality mineral wool surface insulation minimizes radiation losses. At the customer's request, the boiler can be equipped with a built-in or free-standing economizer, as well as a condensing heat exchanger.

Equipment:

The hot water boiler can be offered as part of a fully equipped functional module, including the boiler body, burner device, exhaust gas heat exchanger (economizer), as well as control and safety systems.

Basic equipment


The scope of delivery depends on the customer’s preferences

Boiler room components:

  • WTM water treatment module
  • Exhaust gas heat exchanger ECO 1/7
  • Exhaust gas heat exchanger ECO 6 for use as a condensing heat exchanger
  • Flow/return connection pipes SP/RP
  • RTS return temperature maintenance devices
  • Fuel supply module GRM
  • Liquid fuel supply module OCM (fuel circulation module)
  • Liquid fuel supply module OSM (fuel supply module)
  • Boiler control cabinet BCO
  • SCO boiler cascade control cabinet
Boiler type UNIMAT Boiler power Boiler length Boiler width Boiler height Boiler weight without burner (kg)
(kW) (mm) (mm) (mm) 6 bar 10 bar
UT-L (LN)2 750 2680 1324 2170 2200 2300
UT-L 4 1000 2680 1324 2185 2300 2400
UT-L (LN)6 1000 2950 1424 2285 2800 2900
UT-L (LN)8 1250 3220 1524 2385 3300 3400
UT-L 10 1350 2950 1424 2285 2900 3100
UT-L (LN)12 1500 3675 1574 2570 4200 4500
UT-L 14 1900 3220 1524 2520 3500 3700
UT-L (LN)16 2000 3725 1674 2670 4700 5100
UT-L 18 2500 3675 1574 2670 4600 5000
UT-L (LN)20 2500 4075 1724 2820 5300 6100
UT-L (LN)22 3000 4570 1824 2920 6900 7600
UT-L 24 3050 3725 1674 2770 5000 5400
UT-L (LN)26 3500 4700 1924 3020 7700 8600
UT-L 28 3700 4075 1724 2900 5700 6500
UT-L 30 4150 4570 1824 3000 7300 8000
UT-L 32 4250 5090 2124 3300 9300 10800
UT-L 34 5200 4700 1924 3085 8300 9200
UT-L (LN)36 5250 5320 2274 3435 11400 13000
UT-L (LN)38 6000 5520 2424 3585 13400 15700
UT-L 40 6500 5090 2124 3285 10200 11700
UT-L 42 7700 5320 2274 3435 12400 14100
UT-L (LN)44 8000 5980 2574 3735 16000 18600
UT-L 46 9300 5520 2424 3585 14800 16900
UT-L (LN)48 10000 6315 2724 3885 19300 21900
UT-L 50 11200 5980 2574 3765 17800 19900
UT-L (LN)52 12000 7050 2924 4115 24700 27000
UT-L 54 12600 6315 2724 4025 20200 22800
UT-L (LN)56 14000 7530 3224 4525 30800 34400
UT-L 58 14700 7050 2924 4225 25700 28100
UT-L 60 16400 7530 3224 4525 32300 35800
UT-L (LN)62 17500 7980 3424 4725 36700 38800
UT-L 64 19200 7980 3424 4725 37800 39800

general description

The boiler body consists of a cylindrical body located in the center of the flame tube, and around the circumference of the smoke pipes of the second and third strokes.
Thermal insulation layer made of mineral wool under the aluminum protective casing.
The fully hinged front door of the boiler opens to the right and left.
All boiler seams are made by automatic welding. All tests and full acceptance of equipment are carried out at the manufacturer.

Possible boiler configuration:
1. Direct flow flange spacer VL with safety fittings (flow sensor, maximum and minimum pressure switch, pressure gauge, sleeve for temperature sensor);
2. Flange spacer for return flow RL (sleeve for temperature sensor and pipe for connecting the compensation pipeline);
3. Flue gas heat exchanger - economizer (possibly available as an integrated module);
4. LBC boiler control system (provides regulation of the boiler power, maintenance and regulation of the set coolant temperature);
5. LSC boiler control system (cascade control in weather-dependent mode);
6. RT circulation device (mixing pump, electric valve, shut-off valves);
7. Module for maintaining the boiler in “hot” reserve (pump, check valve, shut-off valves and electric valve);
8. WTM water treatment module (control by timer or water quality).
Boilers can be equipped with Dreizler, Saacke, Weishaupt and Oilon burners.

The reliability of the three-pass design of Unimat boilers has been repeatedly proven by examples of their practical application in 140 countries around the world. Fire tube hot water boilers of the UNIMAT series are offered in various sizes and can operate in cascade.


Boilers of the UT-L type can be used in hospitals, private and multi-apartment residential buildings, office buildings, as well as industrial enterprises. Thanks to its high degree of versatility, the UT-L can be used as a backup boiler or used to cover peak loads.

The hot water boiler can be offered as part of a fully equipped functional module, including the boiler body, burner device, exhaust gas heat exchanger (economizer), as well as control and safety systems.

Basic equipment

The scope of delivery depends on the customer’s preferences

Boiler room components:

  • WTM water treatment module
  • Exhaust gas heat exchanger ECO 1/7
  • Exhaust gas heat exchanger ECO 6 for use as a condensing heat exchanger
  • Flow/return connection pipes SP/RP
  • RTS return temperature maintenance devices
  • Fuel supply module GRM
  • Liquid fuel supply module OCM (fuel circulation module)
  • Liquid fuel supply module OSM (fuel supply module)
  • Boiler control cabinet BCO
  • SCO boiler cascade control cabinet

More detailed information O

  • Efficient three-way design
  • Effective thermal insulation, high efficiency
  • Can be used when low temperatures return flow (from 50 °C)
  • The maximum permissible difference between the temperature of the return and forward flow of the boiler is 50 K
  • Permissible minimum boiler load - 10% of rated power
  • Compatible with burner devices from leading global manufacturers
  • Reducing emissions of harmful substances through the use of modern burner devices and careful selection of the combination of boiler and burner
  • Easy maintenance thanks to fully openable front boiler door
  • Absence of turbulators in smoke pipes
  • Suitable for liquefied gas and light liquid fuels
  • Design proven by many years of experience

The flame pipe ends with a rotating chamber of flue gases, washed by water, which passes into the second passage of the smoke pipes. In total, the boiler has three heat exchange passes: the first - in the boiler furnace (radiant heat exchange), the second and third - in the smoke tubes of the boiler (convective). The arrangement of smoke pipes in a circle ensures optimal flow of flue gases. Smoke pipes do not have internal turbulators, which create additional resistance to the movement of combustion products. The combustion chamber, water space, radiant and convective heating surfaces are optimized and mutually coordinated.

The front door of the boiler opens completely. Depending on customer preferences, hinges can be located on the left or right. Thanks to the fully openable boiler door, complete maintenance, cleaning and inspection can be carried out. The absence of turbulators in the second and third stroke pipes reduces the labor intensity and time spent on routine maintenance of the boiler. High-quality mineral wool surface insulation minimizes radiation losses. At the customer's request, the boiler can be equipped with a built-in or free-standing economizer, as well as a condensing heat exchanger.

Universal heating boilers Bosch Unimat UT-L are designed to operate on gas and light liquid fuel. The use of condensation technology makes it possible to use the heat released during combustion as efficiently as possible, while reducing harmful effects on environment. The block design and other configuration features make their use optimal for large objects - industrial enterprises, hospitals, thermal power plants, factory floors.

Main advantages

  • Bosch Unimat UT-L boilers have a traditional German quality, designed in accordance with TRD 300 standards, are safe if the installation and operation rules are followed. Production in Russia ensures absolute technical adaptation and the ability to combine with the equipment used when installing or modernizing a heat supply system.
  • A wide power range (650-19200 kW) and the ability to choose the design of the heat exchanger allow you to ideally adapt the boiler to the room parameters and climatic conditions. It is possible to connect several boilers in parallel or in series into a single installation with a corresponding increase in power.
  • Environmental friendliness with maximum heat transfer is achieved thanks to the principle of three-pass passage of combustion products. Even when using liquid fuel, the emission of harmful substances is kept to a minimum.
  • The compact design and lightweight alloys used simplify transportation and installation of the boiler. At the consumer's request, the front door and burner can be hung on the right or left. The channel frame at the base of the boiler makes possible installation without an additional foundation (if the boiler room has a flat floor).
  • Modern engineering developments optimize thermal loads on the housing, increasing reliability and extending the service life of the equipment.
  • Characterized by high efficiency due to the extreme reduction of probable heat losses and the use of latent heat of flue gases. Condensing technology allows achieving efficiency above 100%.

Bosch Unimat UT-L boilers combine excellent specifications with ease of maintenance. The design provides for accessibility of the combustion chamber and additional surfaces heating, easy cleaning, possibility of inspection of the rotary chamber. Additional comfort is provided by individual configuration selection.

For ease of operation, a coordinated control system for the heating circuit, boiler and burner is used, depending on user requirements and design, adapted to various software applications. Using the SMS-930 functional module allows you to control an installation that includes up to 8 boilers with general or separate coordination of the operation of each of them.

Design overview

Bosch Unimat UT-L boilers various models designed for combustion of natural gas or liquid fuel in accordance with the standard for coolant production low pressure. Universality of application is achieved by the ability to complete design modules and optional equipment according to user needs.

  • The boiler casing is made of structured (corrugated) aluminum sheet.
  • The boiler and burner door are carefully insulated (insulation layer 100 mm).
  • The return flow lines, drains and safety valves are connected through fittings.
  • The flue gas collector is equipped with a lower control hatch.
  • When heating water in the heating system above 110 o C, an automatic safety limiter is triggered.
  • Delivery is variable: assembled with burner and boiler or separately.
  • The heat exchanger can be built-in or free-standing.

The three-pass passage in the heat exchangers ensures uniform heating of surfaces and maximum energy output combined with low emissions of harmful substances. This constructive solution guarantees a high utilization rate of Bosch Unimat UT-L boilers.

Table. dimensions flue gas heat exchanger for Bosch Unimat UT-L boilers

Heating boiler type Unimat UT-L

Maximum power, kW

Dimensions, mm

Flue gas connection, mm

Support frame, mm

H5 channel

UT38/6000(LN) 4)

UT44/8000(LN) 4)

UT48/10000(LN) 4)

UT52/12000(LN) 4)

UT56/14000(LN) 4)

UT62/17500(LN) 4)

1) Dimension L1 is indicative and depends on the burner manufacturer, design, and actual heat output. If the scope of supply includes a flue gas heat exchanger, the corresponding length must be taken into account according to technical passport DA170 / DA171.

2) Minimum transport dimensions with dismantled fittings, burner and terminal box (without cable duct; with cable duct + 75 mm on the right).

3) Maximum height taking into account the boiler fittings, lifting eye or door retaining ring.

4) UNIMATIC is located on the side

Share